Now that the MT3809 flow meter is disassembled, let’s review how to remove and mount the transmitters. If you need a refresher on steps one through five, click here for a review.
Step 6: Remove the HART Transmitter
Use the screwdriver to remove the screws in each of the four corners. Then, go ahead and remove the transmitter.
Step 7: Mount the FF Transmitter
Replace the transmitter and use the screwdriver to tighten all four screws in each of the corners.
Step 8: Connect the Wiring Again
Connect the FF wiring to the terminal strip (refer to :41 in the video for a complete diagram). It is important to note that for FF, connect the wiring to pp11(+) and 13 (-). The FF wiring is different for HART. If helpful, watch how I thread and secure the wiring throughout the Transmitter Terminal Strip at :45 in the video. Finally, mount the terminal strip.
Step 9: Mount the Needle
Set the needle and tighten the screw underneath.
Steps 10 and 11: Connect the LCD Flatcable and Mount the Top Scale
Connect the LCD flatcable and mount the top scale. Be sure the washers are on top of the scale. Then, tighten the select screws.
To view in full screen mode, simply click the YouTube icon after pressing play.
Ready for the final tutorial in this series? View this video to learn how to configure the transmitter and mount the bottom scale and cover. As always, contact our Technical Services team for local support wherever you are around the globe.